Philips EB-Ci 36W Ballast 220-240V
The Philips EB-Ci 36W Ballast is an electronic control gear made for TLD fluorescent lamps. It supports 1–2x36W or 1–4x18W tubes. Because it operates on 220–240V power, it works well in most commercial lighting systems.
Developed by Philips, this ballast delivers stable and smooth lamp performance. As a result, lights turn on quickly and remain steady during use. Also explore our Electronic Ballasts range for other wattage options.
Why Choose Philips EB-Ci 36W Ballast?
First, this ballast ensures fast and flicker-free starting. Unlike traditional magnetic ballasts, it reduces visible light flicker. Therefore, it creates a more comfortable environment in offices and classrooms.
In addition, it controls electrical current efficiently. Because of this, lamps last longer and perform better. Moreover, the unit runs quietly, which makes it suitable for indoor spaces.
Energy Efficiency Benefits
Electronic ballasts use power more efficiently. As a result, electricity costs can decrease over time. Furthermore, they generate less heat during operation.
Not only does this improve safety, but it also supports longer system life. Therefore, it is a smart choice for modern lighting upgrades.
Applications of Philips EB-Ci 36W Ballast
This ballast is ideal for many settings. For example:
Office lighting systems
Retail stores
Schools and institutions
Commercial buildings
Industrial fluorescent fixtures
Since it supports multiple lamp combinations, it offers flexibility for different installations.
Easy Installation Process
The compact design allows simple fitting inside compatible fixtures. First, switch off the power supply. Then, connect the wiring according to the fixture diagram. After that, secure the ballast firmly in place.
Because it follows standard design specifications, replacement remains quick and convenient.
Reliable Performance
If you need steady and energy-saving lamp control, this ballast is a dependable option. In summary, it provides smooth ignition, stable brightness, and efficient power use.
Therefore, the Philips EB-Ci 36W Ballast remains a trusted solution for professional lighting systems
General Information
| Lamp Type | TL-D |
| Number of Lamps | 1-4 piece/unit |
| Suitable For Outdoor Use | No |
| Number of Products on MCB (16A Type B) (Max) | 28 |
| Automatic Restart | Yes |
Operating and Electrical
| Input Voltage | 220-240 V |
| Input Frequency | 50 or 60 Hz |
| Operating Frequency (Nom) | 42-60 kHz |
| Ignition Method | Warm Start |
| Crestfactor (Max) | 1.7 |
| Ignition Time (Nom) | 1.0 s |
| Mains Voltage Performance (AC) | -10%-+10% |
| Mains Voltage Safety (AC) | 198…264V |
| Earth Leakage Current (Max) | 0.5 mA |
| Inrush Current Width | 0.35 ms |
| Ballast Factor (Nom) | 1 |
| Power Factor (Max) | 0.98 |
| Power Factor (Min) | 0.90 |
| Input Power (Max) | 70.2 W |
| Input Power (Min) | 21.3 W |
| Power Losses (Max) | 6.2 W |
| Power Losses (Nom) | 3.3 W |
| Inrush Current Peak (Max) | 19 A |
| Rated Lamp Power | 18-36 W |
Wiring
| Connector Type Input Terminals | Insert |
| Cable Capacity Output Wires Mutual (Max) | 150 pF |
| Connector Type Output Terminals | Insert |
| Cable Length Hot Wiring | 0.75 m |
| Wire Striplength | 7.5-8.5 mm |
| Input Terminal Cross Section | 0.50-1.50 mm² |
| Output Terminal Cross Section | 0.50-1.50 mm² |
| Cable Capacity Output Wires to Earth (Max) | 150 pF |
| Connector Type | Insert |
System characteristics
| Rated Lamp Power on TL-D | 18-36 W |
| System Power on TL-D | 21.3-68.2 W |
| Lamp Power on TL-D | 18.0-31.0 W |
| Power Loss on TL-D | 3.3-6.2 W |
Temperature
| T-Ambient (Max) | 50 °C |
| T-Case Lifetime (Max) | 75 °C |
| T-Case Maximum (Max) | 75 °C |
| T-Ignition (Max) | 50 °C |
| T-Ignition (Min) | -10 °C |
Mechanical and Housing
| Housing Material | Plastic |
| Housing | L210x30x26mm |
Emergency Operation
| Battery Voltage Lamp Ignition | 165-253 V |